model_icon
(13-14) VFD System with Powered Dampers and Pressure Transmitter - Type 3
Lev-co’s LEVEL 3 VFD system allows for “On-Demand” flow control of an exhaust fan for industrial ventilation applications.
FUNCTION:
  • The fan is first activated by an "Optional" switch attached to the hose reel or hose drop. When this switch closes the fan turns on and opens the first motorized damper.
  • Once the damper in the 1st drop opens, a digital pressure transmitter senses the pressure in the main duct downstream of the fan and allows the VFD to actively control motor speed as a function of duct (negative) pressure.
  • As more dampers are opened and closed the fan speed increases and decreases in order to provide the required flowrate at each drop. This permits constant, effective exhaust at a target duct pressure no matter how many dampers are open or closed. Flow "On Demand"
  • As each hose reel or hose drop returns to its stored position, the damper on each drop closes.
  • The fan turns off when the last operator returns the hose to its stored/recoiled position
    The following components are included in this “Level 3” VFD solution:
  • VFD (Variable Frequency Drive) IP55
  • Control Panel IP55 complete with with the following components
  • HOA Manual/Off/Auto selector switch
  • Step-Down transformer used to supply 24 volt dampers
  • ”Fan on” Pilot Light
  • Pressure Transmitter 4-20 ma
  • Pressure Gauge 1-10” WG
  • 100’ of pneumatic tubing
  • 1/8” MPT hose barb (for connection to duct)
  • Main System / Part
    Part # Description
    CP13-14-30-575/10/20-IP55 Type 3 Control Panel,NEMA 12.
  • Panel only. Drive ordered separately
  • System Voltage: 575/3/60 Volts
  • Drive Power: 10 HP
  • Drive Rating: IP55
  • Working Pressure: 20 in wc
  • CP13-14-30-VFDO-208/1.5/20-IP55 Type 3 VFD Control Panel,NEMA 12.
  • Drive type: Optidrive
  • System Voltage: 208/3/60 Volts
  • Drive Power: 1.5 HP
  • Drive Rating: IP55
  • Working Pressure: 20 in wc
  • CP13-14-30-VFDO-208/3/5-IP55 Type 3 VFD Control Panel,NEMA 12.
  • Drive type: Optidrive
  • System Voltage: 208/460/3/60 Volts
  • Drive Power: 5 HP
  • Drive Rating: IP55
  • Working Pressure: 20 in wc
  • CP13-14-30-VFDO-575/1.5/20-IP55 Type 3 VFD Control Panel,NEMA 12.
  • Drive type: Optidrive
  • System Voltage: 575/3/60 Volts
  • Drive Power: 1.5 HP
  • Drive Rating: IP55
  • Working Pressure: 20 in wc
  • CP13-14-30-VFDO-575/10/20-IP55 Type 3 VFD Control Panel,NEMA 12.
  • Drive type: Optidrive
  • System Voltage: 575/3/60 Volts
  • Drive Power: 10 HP
  • Drive Rating: IP55
  • Working Pressure: 20 in wc
  • CP13-14-30-VFDO-575/3/20-IP55 Type 3 VFD Control Panel,NEMA 12.
  • Drive type: Optidrive
  • System Voltage: 575/3/60 Volts
  • Drive Power: 20 HP
  • Drive Rating: IP55
  • Working Pressure: 20 in wc
  • CP13-14-30-VFDO-575/3/3-IP55 Type 3 VFD Control Panel,NEMA 12.
  • Drive type: Optidrive
  • System Voltage: 575/3/60 Volts
  • Drive Power: 3 HP
  • Drive Rating: IP55
  • Working Pressure: 20 in wc
  • CP13-14-30-VFDO-575/3/5-IP55 Type 3 VFD Control Panel,NEMA 12.
  • Drive type: Optidrive
  • System Voltage: 575/3/60 Volts
  • Drive Power: 5 HP
  • Drive Rating: IP55
  • Working Pressure: 20 in wc
  • CP13-14-30-VFDO-575/50/20-IP55 Type 3 VFD Control Panel,NEMA 12.
  • Drive type: Optidrive
  • System Voltage: 575/3/60 Volts
  • Drive Power: 50 HP
  • Drive Rating: IP55
  • Working Pressure: 20 in wc
  • CP13-14-O-208/3/60-5-2-20-50-32 Type 3 VFD Control Panel,NEMA 12.
  • Drive type: Optidrive
  • System Voltage: 208/3/60 Volts
  • Drive Power: 5 HP
  • Drive Rating: IP55
  • Working Pressure: 20 in wc
  • Control Transformer: 50 VA
  • Fused Disconnect: 32 Amps
  • P-025-XCPA-0109A9A-N4-10HP Custom Enclosed Panel Assembly • 1x 60A Non-Fusible Disconnect – Rotary Type • 1x Line Side Fuse Holders (Fuses Included) • 1x Hand/Off/Auto Selector Switch • 1x “High Temp” Pushbutton • 1x Green LED Pilot Light – 24V • 2x Red LED Pilot Light – 24V • 2x Control Relays • 1x Buzzer • Terminal Blocks • English Labelling • 600 – 24V Control Transformer – 100VA (Fuses Included) • 600 – 240V Control Transformer – 500VA (Fuses Included) • NEMA 4/12 Metal Enclosure – Ventilated • Wired, Assembled & ETL/UL/CSA Approved • Made in Canada!
    P-025-XCPA-1204E9A-N4-10HP Control panel for the hose reel and fan. The panel shall allow the manual or automatic start, stop, and speed control of the Fan and provide power to the hose reel motor. The controls shall be designed for a maximum load of a 10 HP fan at 575V/3/60 and 350 Watt 230/1/60 hose reel motor and various controls.
    XCPA-0109A9A-N4 • Custom Enclosed Panel Assembly • 1x 60A Non-Fusible Disconnect – Rotary Type • 1x Line Side Fuse Holders (Fuses Included) • 1x Hand/Off/Auto Selector Switch • 1x “High Temp” Pushbutton • 1x Green LED Pilot Light – 24V • 2x Red LED Pilot Light – 24V • 2x Control Relays • 1x Buzzer • Terminal Blocks • English Labelling • 600 – 24V Control Transformer – 100VA (Fuses Included) • 600 – 240V Control Transformer – 500VA (Fuses Included) • NEMA 4/12 Metal Enclosure – Ventilated • Wired, Assembled & ETL/UL/CSA Approved • Made in Canada! • Thermocouple Relay to be Supplied
    XCPA-1204E9A-N4 • Custom Enclosed Panel Assembly • 1x 60A Non-Fusible Disconnect – Rotary Type • 1x Line Side Fuse Holders (Fuses Included) • 1x Hand/Off/Auto Selector Switch • 1x “High Temp” Pushbutton • 1x Green LED Pilot Light – 24V • 2x Red LED Pilot Light – 24V • 2x Control Relays • 1x Buzzer • Terminal Blocks • English Labelling • 600 – 24V Control Transformer – 100VA (Fuses Included) • 600 – 240V Control Transformer – 500VA (Fuses Included) • NEMA 4/12 Metal Enclosure – Ventilated • Wired, Assembled & ETL/UL/CSA Approved • Made in Canada! • Thermocouple Relay to be Supplied
    AD-VFD-230V-2 2.0 HP AC DRIVE ,230V 1/3 PH IN 3 PH OUT
    AD-VFD-230V-3 3.0 HP AC DRIVE , 230V 1/3 PH IN 3 PH OUT
    JRP-VFD-5HP-208v-Nema DISC***Pls use VFD-230V-3-NEMA4 5HP VFD, 208v with Nema 4 Enclosure
    L-14781-575-2-01 VFD Based Fume and Dust Control Panel & Drive. 575V/3/60 2HP. Construction: IP 55
    MWA-VFD-230V-3/N1 3.0 HP AC DRIVE ,230V 1 PH IN 3 PH OUT in NEMA 1 enclosure
    MWA-VFD-230V-5/N1 5.0 HP AC DRIVE ,230V 1 PH IN 3 PH OUT in NEMA 1 enclosure
    MWA-VFD-230V-5/N4 5.0 HP AC DRIVE ,230V 1 PH IN 3 PH OUT in NEMA 4 enclosure
    Fan Control Panels (when ordering main unit)
    Part # Description
    OPTI-VFD-15HP-NEMA12-3Panel 3 – Panel NEMA 12, 1 VFD 15HP c/w Panel, HOA, Pressure Transmitter (Lev-co to supply), 4 – 3.0 HP 575V overloads and disconnect
    OPTI-VFD-15HP-NEMA12-5Panel 5 – Panel NEMA 12, 1 VFD 15HP c/w Panel, HOA, Pressure Transmitter (Lev-co to supply), 4 – 3.0 HP 575V overloads and disconnect
    OPTI-VFD-20HP-NEMA12-1Panel 1 – Panel NEMA 12, 1 VFD 20 HP c/w Panel, HOA, Pressure Transmitter (Lev-co to supply), 1 - 20 HP 575V overloads and disconnect
    OPTI-VFD-2HP-NEMA12-1Panel 1 – Panel NEMA 12, 1 VFD 2HP c/w Panel, HOA, Pressure Transmitter (Lev-co to supply), 5 – 1/3 HP 575V overloads and disconnect
    OPTI-VFD-30HP-NEMA12-2Panel 2– Panel NEMA 12, 1 VFD 30HP c/w Panel, HOA, Pressure Transmitter (Lev-co to supply), 3 - 7.5 HP 575V overloads and disconnect
    VFD-ABB Brand
    Part # Description
    VFD-A250-0.5-115/1/60 ABB 250 VFD 0.5HP 110V 1-Phase 60Hz
    VFD-A250-0.5-220/1/60 ABB 250 VFD 0.5HP 200V 1-Phase 60Hz
    VFD-A250-0.5-220/3/60 ABB 250 VFD 0.5HP 200V 3-Phase 60Hz
    VFD-A250-1.5-115/1/60 ABB 250 VFD 1.5HP 110V 1-Phase 60Hz
    VFD-A250-10-460/3/60 ABB 250 VFD 10HP 380V 3-Phase 60Hz
    VFD-A250-10-575/3/60 VFD 10HP 575V 3-Phase 60Hz
    VFD-A250-1-115/1/60 ABB 250 VFD 1HP 110V 1-Phase 60Hz
    VFD-A250-1-220/1/60 ABB 250 VFD 1HP 200V 1-Phase 60Hz
    VFD-A250-1-220/3/60 1HP 240V VFD 3-Phase 60Hz
    VFD-A250-1-460/3/60 1HP 480V VFD 3-Phase 60Hz
    VFD-A250-15-575/3/60 ABB 250 VFD 15HP 500V 3-Phase 60Hz
    VFD-A250-1-575/3/60 1HP 600V VFD 3-Phase 60Hz
    VFD-A250-2-220/1/60 ABB 250 VFD 2HP 200V 1-Phase 60Hz
    VFD-A250-2-220/3/60 2HP 230V VFD 3-Phase 60Hz
    VFD-A250-2-460/3/60 2HP 480V VFD 3-Phase 60Hz
    VFD-A250-2-575/3/60 2HP 600V VFD 3-Phase 60Hz
    VFD-A250-3-220/1/60 ABB 250 VFD 3HP 200V 1-Phase 60Hz
    VFD-A250-3-220/3/60 3HP 240V VFD 3-Phase 60Hz
    VFD-A250-3-460/3/60 3HP 480V VFD 3-Phase 60Hz
    VFD-A250-3-575/3/60 3HP 600V VFD 3-Phase 60Hz
    VFD-A250-5-220/3/60 5HP 240V VFD 3-Phase 60Hz
    VFD-A250-5-460/3/60 5HP 480V VFD 3-Phase 60Hz
    VFD-A250-5-575/3/60 5HP 600V VFD 3-Phase 60Hz
    VFD-A250-7.5-460/3/60 ABB 250 VFD 7.5HP 380V 3-Phase 60Hz
    VFD-A250-7.5-575/3/60 ABB 250 VFD 7.5HP 500V 3-Phase 60Hz
    VFD-ABB-600 Veriable Frequency Drive with a ABB Control Panel c/w LED push buttons for start/stop & manual potentiometer for speed control with 600V AC input option.
    Reactors for VFD's
    Part # Description
    P-025-LIN-R Line Reactor - 20HP 575/3/60
    2 required per fan, 1 at load, 1 at line
    Motorized Dampers
    Part # Description
    P-108-100 Energy Saver Damper S-MAX 100 MM (4"). For use with Extractor Arms and Vehicle Exhaust Hoses. Damper is electrically operated and micro-switch controlled. (Hood mounted for extractor arm and reel mounted for hose reels micro-switch Model: MS-12 is sold separately.) Ideal for Multi-Station and Multi-Drop applications.
    P-108-150 Energy Saver Damper S-MAX 150 MM (6"). For use with Extractor Arms and Vehicle Exhaust Hoses. Damper is electrically operated and micro-switch controlled. (Hood mounted for extractor arm and reel mounted for hose reels micro-switch Model: MS-12 is sold separately.) Ideal for Multi-Station and Multi-Drop applications.
    P-108-200 Energy Saver Damper S-MAX 200 MM (8"). For use with Extractor Arms and Vehicle Exhaust Hoses. Damper is electrically operated and micro-switch controlled. (Hood mounted for extractor arm and reel mounted for hose reels micro-switch Model: MS-12 is sold separately.) Ideal for Multi-Station and Multi-Drop applications.
    DAMP-MOT-04-120 Ø4" Motorized Damper 120V
    DAMP-MOT-05-120 Ø5" Motorized Damper 120V
    DAMP-MOT-06-120 Ø6" Motorized Damper 120V
    DAMP-MOT-08-120 Ø8" Motorized Damper 120V
    DAMP-MOT-10-120 Ø10" Motorized Damper 120V
    DAMP-MOT-12-120 Ø12" Motorized Damper 120V
    Safety Disconnects for Fans
    Part # Description
    P-025-SAF-D Safety disconnect option, 600V Ac Disconnect 30A Non Fused 3R
    Digital Pressure gauge with 4-20 MA output
    Part # Description
    FI-DPT-0025 Differential pressure transmitter 0 - 2.5 H2O
    FI-DPT-005 Differential pressure transmitter 0 - 5 H2O
    FI-DPT-010 Differential pressure transmitter 0 - 10 H2O
    FI-DPT-020 Differential pressure transmitter 0 - 20 H2O
    Manual Blast Gates
    Part # Description
    IN-BG-04 4" diameter Blast gate
    IN-BG-05 5" diameter Blast gate
    IN-BG-06 6" diameter Blast gate
    IN-BG-08 8" diameter Blast gate
    IN-BG-10 10 diameter Blast gate
    IN-BG-12 12" diameter Blast gate
    Sensors and Switches (when ordering main unit)
    Part # Description
    LS-12 Hood mounted switch for controlling the fan or light.To be used in conjuction with the P-025 Series Control Panel.
    MS-12-24V Micro-switch for the automatic "Start/Stop" of the fan and/or automatic damper. C/W Switch and 24V blue 25MM "RUNNING" light.
    Misc. Options (when ordering main unit)
    Part # Description
    VFD-PLATE Mounting plate for VFD and Control panel. Folded 10GA mild steel. 59" x 18".
    MBS-32-SG320-S4 Fan Motor Control Station, 24-32 Amps
    VFD-575V-25 Variable Frequency drive for 25HP 575/3/60Hz motor
    Accessories
    Part # Description
    CP-ACC-KIT Accessories kit for Type 2 control panel
    Odd Fittings - DP
    Part # Description
    LEV-THMK-H06L01-01 ProSense temperature sensor, Type K thermocouple, hex nipple probe, ungrounded, 6in insertion length, 1/4in probe diameter, stainless steel sheath, 1/2in male NPT process connection, 1/2in male NPT with 3in 24 AWG wire leads.
    LEV-THMK-HSJ ProSense Type K thermocouple connector, high-temperature standard round pin jack, 662 deg F (350 deg C), glass filled thermoplastic body, brown, thermocouple material pins, 32 AWG to 14 AWG wire size range.
    LEV-THMWK-100-03 ProSense Type K thermocouple temperature sensor extension wire, 2 conductors, 20 AWG, PVC conductor insulation material, yellow and red, overall shielded, PVC jacket, yellow, 100ft coil.
    THMK-HSP ProSense Type K thermocouple connector, high-temperature standard round pin plug, 662 deg F (350 deg C), glass filled thermoplastic body, brown, thermocouple material pins, 32 AWG to 14 AWG wire size range.
    XTD-0-UNV ProSense programmable temperature transmitter, isolated, RTD, thermocouple, millivolt or potentiometer input, deg F or deg C, 4-20 mA output, 12 to 35 VDC operating voltage, 35mm DIN rail mount, removable screw terminal plugs.
    - Installation Accessories
    Part # Description
    DPT-020 Differential pressure transmitter 0 - 20 H2O
     
    Other Industries / Processes
    As we understand that our products may need to be re-applied during their life span (+20 years), we have listed below other applications that this product can be used For. Before re-applying any of our solutions, please contact one of our representatives to confirm the suitability of your application.

    Chemicals and Plastics Manufacturing - Resin Manufacturing
    Chemicals and Plastics Manufacturing - Rubber Manufacturing
    Chemicals and Plastics Manufacturing - Soap Manufacturing
    Construction - Concrete Demolition Hammer
    Educational Facilities - Auto Shop
    Educational Facilities - Welding Shop
    Food & Beverage Manufacturing - Canning
    Food & Beverage Manufacturing - Food Packaging Plant
    Food & Beverage Manufacturing - Fruit Production
    Food & Beverage Manufacturing - Refrigeration
    Forensics - Forensics Laboratories
    Heavy and Farm Equipment Repair - Farm Equipment Repair
    Heavy and Farm Equipment Repair - Heavy Equipment Repair
    Machine Shop - Straight Line Automatic Buffing
    Marine - Hull Building
    Mining and Quarrying - Drilling
    Mining and Quarrying - Lead Smelting
    Mining and Quarrying - Nickel Mining
    Miscellaneous Operations - Cigarette and Tobacco Smoke
    Miscellaneous Operations - Mortuary Table
    MRO - Diesel Engines Repair
    MRO - Heavy Equipment Repair
    MRO - Steel Welding
    Museums, Historical Sites, and Similar Institutions - Artifact Cleaning
    Museums, Historical Sites, and Similar Institutions - Paleontology
    National Defense - Military Vehicle Repair
    Painting - Dip Tank
    Painting - Drying Oven Ventilation
    Painting - Large Paint Booth
    Painting - Paint Mix Storage Room
    Painting - Trailer Interior Spray Painting
    Paper and Leather Manufacturing - Paper Bleaching
    Paper and Leather Manufacturing - Paper Pulping
    Process Engineering - Air Cooled Mixer and Muller
    Process Engineering - Banbury Mixer
    Process Engineering - Bucket Elevator Ventilation
    Process Engineering - Mixer And Muller Hood
    Process Engineering - Roller Mill Ventilation
    Public Transportation - Bus Maintenance and Repair
    Public Transportation - Subway Maintenance and Repair
    Public Transportation - Train Maintenance and Repair
    Refineries and Energy - Renewable Energy Manufacturing
    Robotics and Artificial Intelligence - Robot Manufacturing
    The Art's - Cleaning with Solvents and VOC's
    Vehicle Repair Garage - Cars & Small Trucks Repair
    Vehicle Repair Garage - Diesel Engines Repair
    Vehicle Repair Garage - Service Garage Ventilation Overhead
    Vehicle Repair Garage - Truck Repair
    Waste Management - Vehicle Repair Garage
    Welding Shops - Steel Welding
    Woodworking - Wood Briquetting
    Woodworking - Wood Incineration